Knowledge / FAQ

ISO 9001:2015

Certification according to ISO 9001 : 2015

The PCE quality management system has been certified according to the standard ISO 9001 : 2015!

 

ISO_en

CE-marking - low voltage guideline

Purpose:

  • mainly a symbol for free trade in the European Community, 
  • if a product has been traded legally in one of the member countries, it can be traded legally in the whole Community,
  • no quality mark or grade labelling,
  • no sign of conformity to standards; to a certain extent a safety mark, because it indicates the compliance to the fundamental safety requirements.
     

The guidelines determine basic requirements the products have to meet.

The essential points for the CE-identification are:

  • it is obligatory for the producer or the EEC importer to put on the CE-identification label,
  • the producer, EEC-importer must hold the engineering data for the disposal of the authorities.
  • marks of conformity to standards are permitted in addition to the CE-marking but are not necessary.

Applicable directives:


RoHS DIRECTIVE 2011/65/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of June 8th 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment

EMC DIRECTIVE 2014/30/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of February 26th 2014 on the harmonisation of the laws of the Member States relating to electromagnetic compatibility

LVD DIRECTIVE 2014/35/EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of February 26th 2014 on the harmonisation of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits

APPROVALS - THE QUALITY MARKS

There has been created a IECEE CB method for mutual recognition of national approvals.
PCE has tested all important products according to this method. An outline of certificates obtained is listed below for reference:

Pruefzeichen_2026
CEE and IEC

The term „CEE“ generally refers to Industrial Plugs and Sockets that comply with International Standard IEC 60309. CEE is the abbreviation of „International Commission on rules for the approval of Electrical Equipment“.

Conformity to standards

CEE plugs and sockets are internationally normalized by IEC 60309-1, IEC 60309-2 and IEC 60309-4 equivalent to the European Norms EN IEC 60309-1,  EN IEC 60309-2 and EN IEC 60309-4. IEC is the „International Electrotechnical Commission“ - which is the world organization for international standardization of electrical equipment.

CENELEC

European Committee for Electrotechnical Normalization - members are the national electrotechnical committees from Austria, Belgium, Bulgaria, Czech Republic, Croatia, Cyprus, Denmark, Germany, Estonia, Finland, France, Greece, Hungary, Ireland, Iceland, Italy, Latvia, Lithuania, Luxemburg, Malta, Republic of North Macedonia, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovenia, Slovakia, Sweden, Switzerland, Spain, Turkey and the United Kingdom.

SYSTEM

The standard CEE plugs and sockets according to IEC 60309-2 respectively EN IEC 60309-2 are designed in their main dimensions in a way that plugs and sockets with the same rated currents, nominal working voltage ranges, the same number of poles and frequency of different producers are compatible.

In order to prevent the insertion of plugs and sockets of different voltages and frequencies, 12 positions of the earthing contact are assigned to the polarizing slot of the skirt of a socket.

The number with the following letter „h“ indicates the position of the earth contact tube, comparing the frontside of the socket with the face of a clock. The keyway is situated at 6 o’clock. 
 

Position of the earthing contact acc. to IEC / EN IEC 60309-2 – SERIES I

UHR_IEC60309

* not offered by PCEn PCE

1) Clock position not standardized and free for use for special applications
2) Mainly for ship installations
3) Only for refrigerated containers

 

Position of the earthing contact acc. to IEC / EN IEC 60309-2 – SERIES I

Voltage

Frequency

16 A / 32 A / 63 A / 125 A

V

Hz

      2P+E (3p)      

      3P+E (4p)      

      3P+N+E (5p)      

57/100 to 75/130

50 and 60

 

 

4

100 to 130

50 and 60

4

4

 

120/208 to 144/250

50 and 60

 

 

9

200 to 250

50 and 60

6

9

 

200/346 to 240/415

50 and 60

 

 

6

220/380
250/440

50
60

 

 

3

250/440 to 265/460

60

 

 

11

277/480 to 288/500

50 and 60

 

 

7

347/600 to 400/690

50 and 60

 

 

5

380 to 415

50 and 60

9

6

 

380
440

50
60

 

3

 

440 to 460

60

 

11

 

480 to 500

50 and 60

7

7

 

600 to 690

50 and 60

 

5

 

1000

50 and 60

 

8

8

> 50

100 to 300

10

10

10

> 50

>300 to 500

2

2

2

> 50 to 250

           DC             

3

 

 

> 250

DC

8

 

 

supply by isolating
transformer

50 and 60

12

12

12

All rated operating voltage and/or frequencies
not covered by other configurations.

1

1

1

 

CORLOR CODES

For ease of identification of the various voltages and frequencies all CEE plugs and sockets are color coded: 

          Rated operating voltage:              

Color code:

20 - 25 V

violet

40 - 50 V

white

100 - 130 V

yellow

200 - 250 V

blue

380 - 480 V

red

500 - 1000 V

black

> 50 V (100-500 Hz)

green

no color code

grey

Ambient temperature:

  • Plugs and socket-outlets complying with IEC 60884 should be suitable for use at ambient temperatures not normally exceeding +40°C, but their average over a period of 24h does not exceed +35°C, with a lower limit of the ambient air temperature of –5°C and and for P-Nova+, S-Nova, Nautilus, Taurus2, TopTaurus2 series connectors   -25°C in accordance with IEC 60884-1 Annex G.
  • IEC 60309 series and EN IEC 60309 series apply to CEE plugs and sockets which are used at an ambient temperature that does not normally exceed the range from -25°C to +40°C.

 
Temperature resistance:  

  • PCE safety plugs and sockets themselves have a temperature resistance up to +70°C (100°C for 1 hour).
  • PCE CEE plugs and sockets themselves have a temperature resistance of -25°C to +80°C (100°C for 1 hour).

 

 

The IK code is a coding system according to EN 62262 respectively IEC 62262, which defines the degree of protection provided by an enclosure against damaging mechanical loads. 
Each characteristic numerical group of the IK Code represents a load energy value as per the table:

 

Remark:
The IK-test is not part of the IEC 60309 standard for industrial plugs and socket-outlets or the IEC 60884 standard for household plugs and socket-outlets.
PC Electric GmbH has therefore tested the IK-codes of these products in accordance with IEC 62262 and according to the test method of IEC 60068-2-75 Ehc, with conditioning for 48 hours at 40°C and a relative humidity of 95%.

 

IK-Code

   IK01   

   IK02   

   IK03   

   IK04   

   IK05   

   IK06  

   IK07  

   IK08   

   IK09   

   IK10   

Load energy in Joule

0,14

0,2

0,35

0,5

0,7

1

2

5

10

20

 

The contacts are made of a copper-zinc alloy. The most important features are:

  • high electric conducting capacity 15 MS/m (m/Ω mm2)
  • high resistance to extension up to 500 N/mm2 (MPa);
  • high corrosion resistance in areas of: industrial atmosphere, agriculture,...
  • with nickel-plated contacts increased corrosion resistance in areas of: seawater, steam, sulphur hydrides, agriculture, dairies.
  • conform to RoHS-directiv 2011/65/EU
  • PCE sockets 63A and 125A have a CuBe lamellar spring for a well contacting and anti-corrosion contacts.

 

Our plugs and sockets are produced from POLYAMIDE 6 as well as PC/ABS.

The main characteristics of these materials are:

  • excellent impact resistance combined with high rigidity and solidity
  • high thermal stability (self-extinguishing)
  • very good insulating qualities
  • high disruptive strength
  • high abrasion resistance
  • high weathering resistance
  • UV-resistance according ISO 4892-2
  • very good chemical resistance to various chemicals
  • free from cadmium and halogen (fluorine, chlorine, bromine, iodine, astatine)
  • conform to RoHS-directive 2011/65/EU
Kunststoffe_EN

A locking device prevents unintended withdrawal by locking the hinged lid in a lug/cavity or a bayonet system with a bayonet ring. According to IEC 60309-2 and EN IEC 60309-2 the following locking devices have to be provided:

rated current protection degree sockets plugs and appliance plugs
16 A and 32 A IP44 hinged lid lug/cavity
16 A and 32 A IP67 bayonet system lug/cavity and byonet ring
63 A and 125 A IP67 bayonet system bayonet ring

Dimensions from the standard EN IEC 60309-2 for the mounting flanged plugs:

Haltevorrichtung

Positioning table [mm]:

Amp.

Poles

E1

L2

L3 (IP44)

L3 (IP67)

T

V

16

3

29-31

>=75

40-41

37-38

>=4

>=8

16

4

33-35

>=80

46-47

43-44

>=5

>=8

16

5

37-39

>=90

52-53

49-50

>=7

>=8

 

 

 

 

 

 

 

 

32

3

39-41

>=90

53-54

50-51

>=7

>=8

32

4

39-41

>=90

53-54

50-51

>=7

>=8

32

5

44-46

>105

58,5-60

55,5-57

>=8

>=9

>> PILOT CONTACT

The pilot contact for levels of current from 63A to 125A is an auxiliary contact (with delayed close when inserted and leading open when pulled) and is used as an electrical interlock. An interlock prevents inserting and pulling under load. 

Technical data of the pilot contact:
Connection type: screw terminal
Wire flexible / solid: 1 - 2,5 / 1 - 4 mm²
Contact screws: 100 Ncm
Rated current: 2 A

CEE connectors and socket-outlets with pilot contact have longer phase contacts and do not guarantee safety from finger-touch (125A). This must be done by an interlock.

 

>> PCS (PILOT CONTACT SYSTEM)

The PCS is a built-in auxiliary contact, used only for 63A and 125A socket-outlets, for protective electrical interlocking or for additional control purposes, with isolated connection in the socket-outlet. CEE sockets have longer phase contacts and guarantee no finger protection (125A), this must be fulfilled by a locking.

The PCS provides the following advantages:

  • no special cable required for the plug
  • isolated inserting and pulling

Technical data:
contacts: silver-coated
wires: 2x YF 1.5 mm², length = 450mm
rated current: 2A

 

Pilot_PCS_system

Ingress protection is tested according IEC / EN 60529. CEE-plugs and sockets with rated current 16A, 32A and 63A are offered in IP44, IP44/54, IP67 or IP66/67 and 125A in IP66/67.
>> The degree of protection is tested on sockets a with and without inserted plug or appliance plugs and 
>> plugs and appliance plugs, when fully inserted into the socket.

 

1st digit

 

Protection against ingress
of solid objects

        

2nd digit

Protection agains penetration of water

2

 

Ø 12,5 mm

 

0

non protection

3

 

Ø 2,5 mm

 

3

spraying water at an angle up to 60° from the vertical

4

 

Ø 1 mm

 

4

splashing water from any direction

5

 

dustproof

 

5

water jets from any direction

6

 

dust-tight

 

6

strong water jets from any direction

 

 

 

 

7

temporary immersion in water under defined pressure and time

 

 

 

 

8

continous submersion in water under defined pressure and time

 

 

 

 

9

high water pressure and high temperature

Example: IP44

1st digit = 4 --> protection against solid objects larger than 1 mm Ø
2nd digit = 4 --> protection against splashing water from any direction

If the system allows plugs of a certain IP rating to be introduced into socket-outlets having another IP rating, attention should be drawn to the fact that the resulting degree of protection of the combination plug/socket-outlet is the lower of the two.

Explanation for double marking IP44/54:
Although protection class IP54 includes the requirements of protection class IP44, double labeling is used because the product standard for CEE plugs and sockets requires IP44 to be specified.

Explanation for double marking IP66/67 and IP66/68:
Up to and including the second digit 6 (protection against powerful water jets), IEC/EN 60529 stipulates that this also fulfills the requirements of all lower digits. Enclosures that are protected against both powerful water jets (second digit 6) and temporary immersion in water (second digit 7) are marked IP66/67.
Enclosures that are protected against both powerful water jets (second digit 6) and continuous immersion in water (second digit 8) are marked IP66/68.